Guides / Refrigerant leak rate calculator (EPA HFC leak repair rule)

Refrigerant leak rate calculator (EPA HFC leak repair rule)

By Emre, Pulad Labs · Updated 2026-11-21

Enter the full charge and how much refrigerant you just added. The calculator shows the leak rate by both EPA methods, compares it with the threshold for the appliance type, and gives the 30-day repair date. Everything runs in your browser.

Leak rate, annualizing method–
Leak rate, rolling average–
Threshold for this appliance–
Result–
Repair deadline if over (30 days)–

Applies to appliances with 15 lb or more of an HFC (or certain substitutes) from January 1, 2026. Check the exact formulas and exceptions in 40 CFR 84.102 before relying on a result.

Free refrigerant leak repair log

One log per appliance. Copy it into a spreadsheet or print it for the service van.

REFRIGERANT LEAK REPAIR AND SERVICE LOG (keep 3 years)
Owner / site: [ ]                         Appliance ID / location: [ ]
Type: [ ] commercial refrigeration (20%)  [ ] comfort cooling / other (10%)  [ ] industrial process refrigeration (30%)
Refrigerant: [R-410A / R-404A / R-134a / ...]     Full charge: [__] lb     Method: [ ] annualizing  [ ] rolling average

Date | Technician (cert. no.) | Lb added | Lb recovered | Leak rate (%) | Over threshold? | Leak location found | Repair done | Initial verification (date / pass) | Follow-up verification (date / pass) | Notes
[ ]  | [ ]                    | [ ]      | [ ]          | [ ]           | [ ] yes [ ] no  | [ ]                 | [ ]         | [ ]                                | [ ]                                   | [ ]

If over threshold: repair within 30 days (120 if an industrial process shutdown is needed), then initial and follow-up verification tests.
Not repaired in time or still leaking: retrofit / retirement plan within 30 days.
Leaked 125% or more of full charge in a calendar year: report to EPA by March 1.

General information, not legal advice. Based on EPA's January 2026 leak repair fact sheet for 40 CFR Part 84 Subpart C; rules and exemptions can change, so check EPA guidance for your equipment.

Want leak rate math, 30-day repair reminders and 3-year records in a phone app?

Frequently asked questions

When do I have to calculate the leak rate?

Under EPA's Emissions Reduction and Reclamation rule, owners or operators must calculate the leak rate each time refrigerant is added to an appliance with a full charge of 15 lb or more of an HFC or certain substitutes, starting January 1, 2026 (with limited exceptions).

What are the leak rate thresholds?

30% for industrial process refrigeration, 20% for commercial refrigeration, and 10% for comfort cooling and other appliances. Above the threshold, the leak must be repaired within 30 days (120 if an industrial process shutdown is needed) and verified.

How long do records have to be kept?

Three years, on paper or electronically, unless the rule says otherwise. Appliances that leak 125% or more of their full charge in a calendar year must also be reported to EPA by March 1.