Guides / F-gas log book template and leak check calculator (UK)

F-gas log book template and leak check calculator (UK)

By Emre, Pulad Labs · Updated 2026-11-21

Pick the refrigerant and enter the charge to see the CO2 equivalent and how often the system must be leak checked. Then keep one log book page per system.

CO2 equivalent–
Leak check frequency–
Automatic leak detection required?–

tCO2e = kg x GWP / 1000. Based on the F-gas rules that apply in Great Britain; Northern Ireland follows the EU regulation. Check the current GOV.UK guidance before relying on a result.

Free F-gas log book page

Copy it into a spreadsheet or print it and keep it with the system.

F-GAS EQUIPMENT RECORD (LOG BOOK)                    Keep for at least 5 years
Operator: [company, site address]          Equipment ID / location: [ ]
Equipment type: [ ] refrigeration  [ ] air conditioning  [ ] heat pump  [ ] other: [ ]
Refrigerant: [R-410A / R-404A / R-32 / ...]   Charge: [__] kg   GWP: [ ]   tCO2e: [ ]
Hermetically sealed: [ ] yes  [ ] no      Automatic leak detection fitted: [ ] yes  [ ] no
Leak check frequency: every [__] months      Next check due: [ ]

Date | Engineer (name, company, F-gas cert. no.) | Work done (leak check / repair / service / recovery / top-up / decommission) | Kg added | Kg recovered | Leak found? where | Repair done | Follow-up check (within 1 month) | Notes
[ ]  | [ ]                                        | [ ]                                                                        | [ ]      | [ ]          | [ ]               | [ ]         | [ ]                              | [ ]

Recovered refrigerant sent to: [company, waste transfer note no.]

US equipment: see the refrigerant leak rate calculator for the EPA 2026 rule.

General information, not legal advice. Thresholds and record rules come from the F-gas regulations that apply in Great Britain; check GOV.UK for the current rules.

Want leak rate math, 30-day repair reminders and 3-year records in a phone app?

Frequently asked questions

Do I need an F-gas log book?

Operators of equipment containing F-gases at or above 5 tonnes CO2 equivalent (10 tCO2e for hermetically sealed systems) must keep records for each piece of equipment: refrigerant type and quantity, every addition and recovery, leak checks, repairs and the engineer who did the work.

How often do leak checks have to be done?

In Great Britain: 5 tCO2e or more every 12 months, 50 or more every 6 months, 500 or more every 3 months. Automatic leak detection halves the frequency, and it is mandatory at 500 tCO2e or more.

How do I work out tCO2e?

Multiply the charge in kg by the refrigerant's GWP and divide by 1000. For example 10 kg of R-410A (GWP 2088) is 20.9 tCO2e, so it needs a leak check at least every 12 months.